RS485 Dual Relay Outputs Data Loggers & Recorders

Features Include:

  • Analog inputs: programmable for thermocouples (J, K, T, E, N, R, S, B), Pt100, mV, V, mA
  • Cold junction compensation for thermocouples and compensation for Pt100 3-wire cables
  • Open loop detection for thermocouples, Pt100 and mV
  • Sampling rate for 1 analog input: 10Hz for mV, V and mA. 5 Hz for t thermocouples and Pt100<
  • Analog input resolution: 17 bits
  • Digital inputs: in voltage, 4 to 35 V to activate. Internally limited current in 5 mA
  • Digital outputs: 8 A / 250 Vac SPDT relay, resistive load
  • Power: 10 to 35 Vdc,  50 mA maximum current
  • 2-wire RS485 communication with Modbus RTU protocol. Configurable address and baud rate (1,200 to 115,200bps)
  • LED indicators for communication and status
  • Key for resetting communication parameters to original factory default
  • Accuracy (at 25 °C): Pt100, mV, V and mA: ±0.15 % of full scale. Thermocouples: ±0.25 % of full scale
  • Temperature effect: 0.003 % of full scale/°C
  • Cold junction compensation for thermocouples: 1 °C at 25 °C. ±0.05 °C / °C
  • Isolation: 1000 Vac from inputs (analog or digital) and power or communication
  • Windows based configurator software (free download)
  • Dimentions: 72 x 78 x 19 mm
  • Mounting: 35 mm DIN rail