8812120000

8812120000

Alt: Complete FieldLogger, Ethernet, USB, 100-240VAC

$1,195.00

FieldLogger Data Logger, 8 I/O, 512K Ethernet, Up to 32 Configurable Alarms, USB, 2xRS485

Minimum Purchase:
1 unit
Adding to cart… The item has been added
Description

Features Include:

  • 8 digital I/Os (individually configured as input or output)
  • 2 relay outputs (NO, NC and common)
  • USB-device interface for configuring, monitoring and download
  • USB-host interface for logged data retrieval through a USB flash drive

8 universal analog input channels:

  • Thermocouples, V, mV, mA, Pt100 and Pt1000
  • Reading and logging rates of up to 1000/second
  • 4 bit A/D conversion resolution

RS485 interface (Modbus master or slave).

  • When acting as a master, can read up to 64 registers from other slaves
  • Registers read can be used in logging, alarms or mathematical operations

Ethernet interface with a lot of services available:

  • Sends alarm warning e-mails (SMTP)
  • Provides web pages with channels and status information (HTTP)
  • Allows logged data download via FTP (client and server)
  • Accesses status and channels values through network management software (SNMP and traps)
  • Allows Modbus communication by ethernet interface (Modbus TCP)

Up to 32 configurable alarms, Alarm actions can include:

  • Activating relays
  • Activating digital outputs
  • E-mails sending to multiple receivers
  • Sending SNMP traps
  • Starting and/or stopping loggings

Up to 128 virtual channels:

  • Basic mathematical functions to be applied on other channels: sum, subtraction, multiplication, division, logic (AND, OR and exclusive OR), square root and power.

24 Vdc output for powering up to eight 4-20 mA transmitters:

  • AC power (100 to 240 Vac)
  • DC Power (19 to 30 Vdc) optional (2011)

Detachable human-machine interface (optional):

  • Keypad and color TFT QVGA display
  • RS485 communication with FieldLogger

Loggings:

  • Up to 100 channels can be logged at a configurable rate
  • Data download through the configuration software or through the freely distributed download DLL